Yes. There are four supply levels: Enclosure Only (Interface-Ready) prepares the openings, base support points and penetrations to your genset data; Subsystem Integration and Factory-Integrated Module add the acoustic lining, airflow, exhaust, fuel, power and lighting, and fire protection, giving a genset-ready enclosure in which the genset is placed and connected on arrival.




Genset Enclosure (20 ft / 40 ft)
For genset OEMs and packagers — enclosure manufacturing and subsystem integration, delivered genset-ready, from enclosure-only to OEM/ODM.
Key Metrics
Product Features
Genset-Ready
Acoustic lining, airflow, exhaust supports, fuel and power are installed and factory-checked; on site the genset is only placed and connected.
Genset-Ready
Acoustic lining, airflow, exhaust supports, fuel and power are installed and factory-checked; on site the genset is only placed and connected.
Any Genset Brand
The layout comes from the genset maker's outline, weight, cooling and exhaust data, so common brands and ratings fit, and a new model gets its openings and supports reworked the same way.
Noise to Your Limit
A tighter noise limit means thicker lining and higher-grade louvers and silencers, from industrial yards to data centres next to homes.
Service Access
Personnel, side service and end doors follow the routes for radiator-core changes, engine overhauls and daily checks; a viewing window shows the controller without opening up.
Fuel Containment
Base tank, day tank and drip tray are sized to the run time and the bunding rules of the destination, including the 110% containment the UK and Australia require.
Ships as Standard
High-cube units kept within ISO dimensions get CSC approval per project and lift and ship like any container; roof silencers and other protrusions come off for transport, so no out-of-gauge freight.
Product Details

Airflow path (schematic)
Air enters at the alternator end, passes over the alternator and engine and is pushed through the radiator by the fan, leaving through the end-wall outlet in the genset's own direction of flow. Inlet openings are usually 1.5–2 times the radiator area and outlets no smaller than it; the pressure drop of attenuated louvers, rain hoods and filters counts against the external restriction the genset allows. A sealed duct with a flexible joint links the radiator to the outlet and the floor is closed, so hot air cannot loop back to the inlet. The genset and radiator come from the customer or the genset OEM; ETENZ sizes the openings and ducting from the genset data sheet.

Airflow path (schematic)
Exhaust runs from the engine outlet through a stainless-steel bellows into the silencer; brackets carry the silencer and pipework, so the turbocharger takes no load. The roof penetration has a weather sleeve and the outlet a rain cap that opens with the gas flow; horizontal runs fall away from the engine and a condensate drain sits where the pipe turns upward. Silencer and pipework inside the enclosure are insulated and clad, the silencer grade follows the noise limit, and the whole system is designed to about half of the engine's permitted back pressure.
Walls and roof are lined with 50–100 mm of rock or glass wool behind a perforated facing; doors close on compression latches against continuous seals, and the air openings carry attenuated louvers or splitter attenuators. The genset sits on the isolators its maker specifies, with flexible connections for cables, fuel and exhaust, so less vibration reaches the structure. Noise is built to the customer's limit, typically a target sound pressure level of 85 dB(A) at 1 m or 75 dB(A) at 7 m, stated with distance, load and test method (such as ISO 8528-10).
The genset base follows the maker's support points, isolator type and loads and is tied into the floor frame. Fuel is held in a base tank or a separate day tank sized to the required run time; a drip tray across the floor collects fuel, oil and coolant leaks and drains to an outside connection. The fill point is outside the enclosure, lockable and fitted with a spill box, and an external level display can be added.
The emergency stop is mounted outside, so the set can be stopped without entering. Lighting, sockets and genset heaters run on separate circuits. Lighting is fed from the load side of the transfer switch, so after a mains failure it returns once the genset has started and the switch has transferred; where light is needed through that gap, battery-backed emergency luminaires are added. Power cables enter through a rodent-proof floor entry or a wall gland plate, single-core cables through non-ferrous glands; distribution boards and an ATS are added per project.
Twenty- and forty-foot high-cube units keep their ISO corner castings and lift from them with a spreader bar; custom sizes get lifting points from a structural check. Roof-mounted silencers, ducts and louvers are counted in the structural loads, and the enclosure's weight and centre of gravity are supplied with its documents, so the genset OEM can check lifting and transport once the genset is installed.
Delivery Scope Options
Enclosure Only (Interface-Ready)
Scope 1Built to the genset's outline, weight, support points, cooling and exhaust data, with door openings, air openings, genset base, exhaust and cable penetrations prepared in one pass.
Scope Includes:
Technical Specifications
| Parameter | Specification |
|---|---|
| Dimensions (20 ft high cube) | 6058 × 2438 × 2896 mm · ISO 668 |
| Dimensions (40 ft high cube) | 12192 × 2438 × 2896 mm · ISO 668 |
| Custom sizes | Sized to the genset outline, weight, airflow and service space (project-confirmed) mm |
| Structure and panels | Channel / square-tube steel frame; roof 2.0 galvanized sheet, walls 1.6–2.0 corrugated sheet mm |
| Acoustic lining | Rock or glass wool with perforated facing, 50–100 (to the noise limit) mm |
| Sound pressure level | Target 85 at 1 m / 75 at 7 m (to the customer's limit, lower available) dB(A) · ISO 8528-10 |
| Ingress protection | IP54 / IP55, IP56 available IEC 60529 |
| Corrosion protection | C3 / C4 / C5 (to the site environment) ISO 12944 |
| Fire resistance | 60–120 (to the customer's fire plan) min |
| Ventilation | Attenuated louvers or splitter attenuators, motorized louvers optional; openings sized to the genset airflow and permitted restriction |
| Exhaust | Stainless bellows, silencer brackets, roof sleeve and rain cap; silencer grade to the noise limit |
| Fuel and containment | Base tank or day tank, floor drip tray; containment volume to the destination's rules |
| Electrical interfaces | Lighting, sockets, heater circuits, external emergency stop, rodent-proof floor entry; distribution board and ATS per project |
| Fire protection | Smoke and heat detection with gas suppression, configured per project |
| Transport | ISO-size units: CSC per project; custom sizes ship as out-of-gauge cargo CSC 1972 |
| Design life | 25 years |
| Warranty | 12 (extendable to 24) months |
Product FAQs
A containerized generator is a complete set sold by a genset maker, with the genset already inside. A genset enclosure is the container and the fit-out that house the genset; that is what ETENZ builds, and the genset comes from you or your genset supplier.
It depends on the genset's outline, weight, airflow and service space. A common split is a 20 ft high cube for sets up to around 1000 kVA and a 40 ft high cube for about 1250–2750 kVA; larger sets, lower noise limits or several sets side by side go into wider or taller custom enclosures or combined units.
It is built to your limit: thicker lining and higher-grade silencers and louvers bring the level down, and the usual targets are in the specification table. Please state the distance, load and test method of the limit (for example ISO 8528-10) and send the genset's open-set noise data.
High-cube units kept within ISO dimensions can receive CSC approval per project and lift and ship like a standard container; the roof silencer and other protrusions come off for transport and are refitted on site, keeping the ISO outline. Wider or taller custom enclosures ship as out-of-gauge cargo.
Genset model and rating, outline drawing and weight, radiator airflow and permitted restriction, exhaust outlet size and permitted back pressure, fuel run time, the noise limit (distance, load, method), site ambient temperature, altitude and corrosion class, and the supply level you need. If not everything is ready, the genset model and rating are enough to start.
Mainly the enclosure size, the acoustic package (lining thickness, silencer and louver grade), tank capacity, the electrical and fire protection scope, and the supply level. Quotations are built from the genset data and the noise and run-time requirements.
It depends on the supply level and scope: Enclosure Only is the shortest, and more subsystems or tighter noise limits take longer. A production schedule follows once the data is confirmed.
Yes. Colour, markings, nameplate and documents follow the genset OEM's or packager's brand; that is the OEM/ODM Under Your Brand level.
Related Solutions
Custom Prefabricated Equipment Enclosures
ETENZ turns equipment needs into prefabricated equipment enclosures, combining enclosure manufacturing, electrical interfaces, environmental control, thermal management, fire/security provisions and OEM/ODM delivery.
Related Products