32-Pack BESS Enclosure (20 ft, 6.25 MWh)

For battery manufacturers and BESS integrators: fit 32 packs of 587Ah cells to complete a 6.25 MWh enclosure, delivered from bare shell to OEM/ODM.

Battery Energy Storage StationRenewable Energy Collector Station SupportRenewable Grid-Connection Power Distribution

Key Metrics

6.25MWh
Capacity
20 ft high cube
Format
Liquid cooling
Cooling
FK-5-1-12
Fire suppression

Product Features

Fits 587Ah packs

All 32 rack positions are made for 1P104S packs of 587Ah cells, so the battery supplier can finalize the fit from the envelope drawing and the racks need no changes at assembly.

Product Details

Behind the long-side doors stand 4 rack columns, each with 8 tiers of support arms, for 32 pack positions in total. The arms carry locating grooves, so a pack pushed in along them drops into its groove and is held in position; there is no aisle inside the enclosure. ETENZ designs and builds the posts and arms to the pack outline, mass and fixing points; tier load, clearance and cooling-connection positions are marked on the rack envelope drawing issued at quotation stage.

Side-door battery racks: 4 columns × 8 tiers, 32 pack positions

The liquid-cooling unit fills the upper level of the equipment end across the full enclosure width; its top fans exhaust upward, and the front mesh door opens fully for service. The chiller, distribution pipework, hose quick couplings to every rack and per-rack flow balancing are completed in the factory, while the cold plates and in-pack circuits belong to the battery supplier. Condensation forms when the coolant supply temperature is below the dew point of the cabin air, so the dehumidifier is sized to the cabin moisture load and the lowest supply temperature; cooling capacity follows the heat load provided by the battery supplier.

Below the chiller, the electrical compartment opens through two end doors and is laid out in three parts: the floor-standing perfluorohexanone (FK-5-1-12) extinguishing unit on one side, the fire control panel and BMS master control box on the middle partition, and the DC power section with DC busbars and surge protective devices on the other side. The BMS comes from the customer or battery supplier; LV auxiliary distribution, lighting, sockets and internal wiring are designed to IEC 61439-1/-2. The electrical scope ends at the DC output terminals, and the PCS and all wiring from there on are on the system side.

The perfluorohexanone (FK-5-1-12) piping runs at two levels: cabin-level pipes follow the battery-area roof, marked with the medium and flow direction, and cluster-level pipes drop down the rack posts to each rack column. Smoke and heat detectors and audible and visual alarms sit on the same row of roof panels. ETENZ can supply and install the extinguishing unit or connect a system nominated by the customer; either way, the detection, alarm and release interlock interfaces are completed with the enclosure.

Explosion-proof combustible-gas detectors on the battery-area roof monitor hydrogen, carbon monoxide and other combustible gases released when cells fail. Their signals go to the fire control panel, which can start the exhaust fan to clear gas from the enclosure. Alarm thresholds, staged actions and the sequence with suppression and emergency stop are designed per project; pressure relief and explosion venting are configured from the battery off-gas data and local code.

An industrial air conditioner is built into one of the electrical-compartment end doors to cool and dehumidify the distribution, control and fire-protection equipment, and the door carries a sign warning not to open it during operation. Lighting, door contacts, water-leak and temperature-humidity monitoring come fitted with the enclosure, wired to the master control box and reported through the BMS or EMS communication interface.

Delivery Scope Options

Scope 1

Bare-Shell Supply (Interfaces Reserved)

A 20 ft high-cube enclosure with the long-side doors and equipment-end partition in place, and the chiller support frame, cable openings and earthing terminals prepared to the layout drawing, ready for the customer to integrate the internal systems.

Scope Includes:

20 ft high-cube enclosure with long-side doors
Chiller support frame and electrical-compartment partition at the equipment end
Rock-wool insulation, anti-corrosion coating and door sealing
Cable openings and earthing terminals

Technical Specifications

Overall dimensions (L × W × H)
6058 × 2438 × 2896 (20 ft high cube with CSC approval)
mm · ISO 668
Maximum gross mass
50,000 (CSC-approved rating)
kg
Nominal capacity
6.25 (32 packs of 587Ah cells in 1P104S configuration, about 195 kWh per pack)
MWh
Battery racks
4 columns × 8 tiers, 32 pack positions, non-walk-in; designed and built by ETENZ, with cells and packs supplied by the customer or battery supplier
Thermal management
Whole-enclosure liquid cooling: liquid-cooling unit on the upper level of the equipment end; distribution pipework and hose quick couplings to every rack, with flow balancing; cold plates inside the packs belong to the battery supplier; dehumidifier fitted, plus a door-mounted air conditioner on the electrical compartment
Fire suppression
Perfluorohexanone (FK-5-1-12) clean-agent suppression with cabin-level and cluster-level piping; supplied and installed by ETENZ, or connected to a customer-nominated system
Detection and alarm
Smoke, heat and combustible-gas detection; audible and visual alarms; gas-release indicator outside the door
Exhaust and pressure relief
Exhaust ventilation interlocked with combustible-gas detection; pressure relief and explosion venting configured to battery off-gas data and local code
LV auxiliary systems
LV distribution, lighting, sockets and internal wiring
IEC 61439-1 / -2
In-cabin DC
DC busbars and DC output terminals; electrical scope ends at the DC output terminals
Monitoring and security
Door contacts, water-leak and temperature-humidity monitoring; BMS / EMS communication interfaces
Ingress protection
IP54 / IP55
IEC 60529
Corrosion category
C3–C5 (selected for the site environment)
ISO 12944
Structure and materials
Roof 2.0 mm galvanized sheet, walls 1.6–2.0 mm corrugated sheet, 50 mm rock-wool insulation
Design life
25
years
Factory inspection
Cabin-level inspection: structure, liquid-cooling loop pressure/leak test and run, fire-protection interlocks, LV, IP and earthing
Warranty
12 (extendable to 24)
months

Product FAQs

It is designed for 32 battery packs: 4 rack columns with 8 tiers each. With 1P104S packs of 587Ah cells (about 195 kWh per pack), that adds up to a nominal 6.25 MWh. For fewer packs with more energy in each, see ETENZ's 28-pack 6.25 MWh battery enclosure.

Cells and packs are not included: they come from the customer or the battery supplier, who installs them. ETENZ designs and builds the racks around your pack's outline, mass, fixing points and cooling interfaces; a rack envelope drawing is issued at quotation stage, and the rack design is finalized once the battery supplier has checked it.

The enclosure is a 20 ft high cube built to the ISO outline of 6058 × 2438 × 2896 mm, and the design carries CSC approval with a CSC-rated maximum gross mass of 50,000 kg. The loaded weight depends on the packs installed and is calculated for each project.

The whole enclosure is liquid-cooled. The liquid-cooling unit sits on the upper level of the equipment end and discharges air through the top. ETENZ supplies the chiller, distribution pipework and hose quick couplings to every rack and balances the flow to each rack; the cold plates inside the packs belong to the battery supplier. Cooling capacity is selected from the heat load provided by the battery supplier.

The enclosure uses perfluorohexanone (FK-5-1-12) clean-agent suppression with cabin-level and cluster-level piping, plus smoke, heat and combustible-gas detection, audible and visual alarms and a gas-release indicator outside the door. ETENZ can supply and install the extinguishing unit, or the system can be configured around one nominated by the customer; in both cases the detection, alarm and release interlock interfaces are completed with the enclosure.

The enclosure has ISO corner castings at each corner and is lifted and lashed as a container. Lifting points, rigging and centre of gravity are checked against the loaded weight, and the exact tonnage is confirmed per project.

The enclosure sits on the foundation at its corner-casting positions and is fixed there, with the fixing points and loads given on the general arrangement drawing; foundation design and construction are part of the site works.

Price depends on the delivery tier (bare shell, subsystem integration, finished cabin or OEM/ODM), the corrosion category, whether ETENZ supplies the liquid cooling and fire suppression, and the standards required at the destination. For a quotation, please send the battery pack specification (outline, mass and cooling interfaces), the delivery tier you have selected and the project location.

Related Solutions

Energy Storage & Renewables

BESS Enclosure Manufacturing and Integration

BESS enclosure manufacturer for battery makers and integrators: series-built to your drawings, or battery-ready around your pack with racks, liquid cooling, fire protection and wiring, factory-tested. OEM/ODM available.

Have a project in mind?