It need not be uniform. Five widths are available — 550, 600, 650, 800 and 1000 mm — chosen per cubicle against its rated current and component fit: small feeders take 550 or 600 while large incomers and bus-ties widen as needed. Mixing widths in one line-up is the normal approach and makes the total length shorter than a single-width arrangement. The point to watch is that the busbar has to run continuously across cubicles of different width, and ETENZ works that transition out at drawing stage.

KYN550-12 Metal-Clad Switchgear
For high-capacity substations and station-service projects: KYN550-12 is the ETENZ metal-clad enclosed switchgear rated 12 kV with a 4000 A main busbar and cubicle widths from 550 to 1000 mm, supplied as a standard configured assembly or installed as the primary equipment inside an MV switchgear E-House.
Key Metrics
Product Features
Main busbar 4000 A
The ETENZ KYN550-12 carries a 4000 A main busbar with distribution busbars selectable from 630 to 4000 A. One line-up takes a large incomer and small feeders together, without sectionalising the busbar to derate it.
Main busbar 4000 A
The ETENZ KYN550-12 carries a 4000 A main busbar with distribution busbars selectable from 630 to 4000 A. One line-up takes a large incomer and small feeders together, without sectionalising the busbar to derate it.
Main busbar 4000 A
The ETENZ KYN550-12 carries a 4000 A main busbar with distribution busbars selectable from 630 to 4000 A. One line-up takes a large incomer and small feeders together, without sectionalising the busbar to derate it.
From 550 mm wide
The 550 in the designation is the standard cubicle width. Five steps are available — 550, 600, 650, 800 and 1000 mm — chosen per cubicle against its rated current and component fit, not fixed across the line-up: a small feeder can be narrow while a large incomer widens.
Fits the room
Depths run 1100 to 1650 mm in six steps and heights 2000 to 2300 mm in four. Where switchroom depth or clear height is limited, those two are pinned by the civil conditions first and the busbar and component layout worked out afterwards, rather than the building being made to suit the cubicle.
E-House ready
A KYN550-12 line-up can be delivered as the primary equipment inside an MV switchgear E-House or power module, with line-up arrangement, busbar connections and in-module interfaces detailed by ETENZ and the delivery boundary settled once at contract stage.
Product Details

KYN550-12 model code
The identity part of KYN550-12 reads position by position: K is metal-clad enclosed switchgear, Y is the withdrawable pattern, N is indoor service, 550 is the design code and 12 is the voltage class. The 550 is also this model’s standard cubicle width — designation and width matching is not a coincidence. A complete order designation carries further positions after it: primary scheme number, operating-mechanism code (D for magnetic, T for spring), cubicle width, rated current and rated breaking current, confirmed cubicle by cubicle at quotation.

KYN550-12 model code
Size on this model is a set of tiers rather than one figure: widths of 550, 600, 650, 800 and 1000 mm, depths of 1100, 1340, 1400, 1450, 1500 and 1650 mm, heights of 2000, 2100, 2200 and 2300 mm. Combined with a 4000 A main busbar and distribution busbars from 630 to 4000 A, each cubicle in a line-up can take the width its own load needs — narrow for small feeders, wider for large incomers — which makes the line-up shorter than a single-width arrangement. In practice the switchroom depth and clear height pin the depth and height first, then circuit duty sets each width, and busbar sizes and component layout follow. ETENZ settles all three in one pass against the switchroom layout and circuit schedule.
Delivery Scope Options
Standard configured assembly
Scope 1Standard configured assembly
Cubicles, busbars, breaker trucks, current transformers and basic secondary wiring are built against the confirmed primary scheme and width composition; labelling and standard delivery documents travel with the panels.
Scope Includes:
Standard configured assembly
Scope 1Standard configured assembly
Cubicles, busbars, breaker trucks, current transformers and basic secondary wiring are built against the confirmed primary scheme and width composition; labelling and standard delivery documents travel with the panels.
Scope Includes:
Technical Specifications
| Parameter | Specification |
|---|---|
| Product form | Indoor metal-clad enclosed switchgear |
| Model | KYN550-12 |
| Rated voltage | 12 kV |
| Rated frequency | 50 Hz |
| Main busbar rated current | 4000 A |
| Distribution busbar rated current | 630 / 1250 / 1600 / 2000 / 2500 / 3150 / 4000 A |
| Short-time withstand current | Confirmed per project kA |
| Peak withstand current | Confirmed per project kA |
| 1 min power-frequency withstand | 42 kV |
| Lightning impulse withstand | 75 kV |
| Cubicle width | 550 / 600 / 650 / 800 / 1000 mm |
| Cubicle depth | 1100 / 1340 / 1400 / 1450 / 1500 / 1650 mm |
| Cubicle height | 2000 / 2100 / 2200 / 2300 mm |
| Degree of protection | IP4X; IP2X with the breaker door open |
| Mass | 300, including the withdrawable truck kg |
Product FAQs
It is this model’s main busbar rating, with distribution busbars also available to 4000 A. The typical places that need it are substation main incomers, large station-service supplies in power plants, and any line-up carrying many circuits on one busbar that should not be sectionalised. Where the busbar current falls short, the alternatives are sectionalising or adding a bus-tie, and both add cubicles and floor area. Send the total line-up load and whether sectionalising is acceptable, and whether 4000 A is a requirement or headroom becomes clear.
From the switchroom civil conditions first, with the electrical layout worked out afterwards. Depths run 1100 to 1650 mm in six steps and heights 2000 to 2300 mm in four. The switchroom depth has to take the cubicle depth plus front operating and maintenance space and the truck withdrawal travel, and the clear height has to take the cubicle plus the busbar bridge and top duct. Once those are set, busbar sizes and component layout are arranged in what remains. Send the switchroom layout with clear height and it can be confirmed during quotation.
On capacity and width. A 4000 A main busbar takes KYN550-12, the highest busbar rating in the series. A wide fault range with rated current to 3150 A takes KYN28A-12. A severely limited switchroom area, where 630 to 1600 A is acceptable, takes YF-KYN450-12 at 475 to 550 mm wide and 1100 mm deep. The series page carries the full five-model comparison.
Four things give a preliminary scheme: the single-line diagram, rated voltage and total line-up current, the system fault capacity, and the switchroom dimensions with clear height. For a contract-grade quotation, add each cubicle’s primary scheme and rated current, control supply type and voltage, metering and protection requirements, cable entry arrangement and cable sizes, communication interfaces, and the standards and document list for the destination market.
Yes. Switchgear is supplied as equipment while an MV switchgear E-House or power module is supplied as an enclosure — the first is the panel itself, the second covers the enclosure, equipment layout, auxiliary systems and interface integration. The selectable widths help here, since the line-up can be packed more closely to a given module length. Where it goes inside as the primary equipment, ETENZ details the line-up arrangement, busbar connections and in-module interfaces, and the delivery boundary is settled once at contract stage.
Related Solutions
Prefabricated E-House Project Delivery Solution
ETENZ delivers configurable prefabricated E-House projects for electrical equipment integration, covering enclosure manufacturing, layout, wiring paths, factory checks, interface coordination, and OEM/ODM cooperation.





Related Products

Withdrawable Metal-Clad MV Switchgear - KYN Series

Containerized MV Switchgear E-House

MV Switchgear E-House

KYN□-24 Metal-Clad Withdrawable Switchgear

KYN61-40.5 Metal-Clad Withdrawable Switchgear