KYN550-12 metal-clad enclosed switchgear cubicle

KYN550-12 Metal-Clad Switchgear

For high-capacity substations and station-service projects: KYN550-12 is the ETENZ metal-clad enclosed switchgear rated 12 kV with a 4000 A main busbar and cubicle widths from 550 to 1000 mm, supplied as a standard configured assembly or installed as the primary equipment inside an MV switchgear E-House.

Switchgear Room & Distribution RoomPrimary Equipment E-HouseRenewable Grid-Connection Power DistributionCampus Distribution Room

Key Metrics

12kV
Voltage
4000A
Main busbar
550-1000mm
Width
IP4X
Protection

Product Features

Feature icon

Main busbar 4000 A

The ETENZ KYN550-12 carries a 4000 A main busbar with distribution busbars selectable from 630 to 4000 A. One line-up takes a large incomer and small feeders together, without sectionalising the busbar to derate it.

Feature icon

Main busbar 4000 A

The ETENZ KYN550-12 carries a 4000 A main busbar with distribution busbars selectable from 630 to 4000 A. One line-up takes a large incomer and small feeders together, without sectionalising the busbar to derate it.

Product Details

The identity part of KYN550-12 reads position by position: K is metal-clad enclosed switchgear, Y is the withdrawable pattern, N is indoor service, 550 is the design code and 12 is the voltage class. The 550 is also this model’s standard cubicle width — designation and width matching is not a coincidence. A complete order designation carries further positions after it: primary scheme number, operating-mechanism code (D for magnetic, T for spring), cubicle width, rated current and rated breaking current, confirmed cubicle by cubicle at quotation.

Position-by-position breakdown of the KYN550-12 type designation

KYN550-12 model code

Size on this model is a set of tiers rather than one figure: widths of 550, 600, 650, 800 and 1000 mm, depths of 1100, 1340, 1400, 1450, 1500 and 1650 mm, heights of 2000, 2100, 2200 and 2300 mm. Combined with a 4000 A main busbar and distribution busbars from 630 to 4000 A, each cubicle in a line-up can take the width its own load needs — narrow for small feeders, wider for large incomers — which makes the line-up shorter than a single-width arrangement. In practice the switchroom depth and clear height pin the depth and height first, then circuit duty sets each width, and busbar sizes and component layout follow. ETENZ settles all three in one pass against the switchroom layout and circuit schedule.

Delivery Scope Options

Scope 1

Standard configured assembly

Cubicles, busbars, breaker trucks, current transformers and basic secondary wiring are built against the confirmed primary scheme and width composition; labelling and standard delivery documents travel with the panels.

Scope Includes:
Cubicles and truck units
Busbars and inter-panel links
Basic secondary wiring
Labelling and standard documents
Scope 1

Standard configured assembly

Cubicles, busbars, breaker trucks, current transformers and basic secondary wiring are built against the confirmed primary scheme and width composition; labelling and standard delivery documents travel with the panels.

Scope Includes:
Cubicles and truck units
Busbars and inter-panel links
Basic secondary wiring
Labelling and standard documents

Technical Specifications

Product form
Indoor metal-clad enclosed switchgear
Model
KYN550-12
Rated voltage
12
kV
Rated frequency
50
Hz
Main busbar rated current
4000
A
Distribution busbar rated current
630 / 1250 / 1600 / 2000 / 2500 / 3150 / 4000
A
Short-time withstand current
Confirmed per project
kA
Peak withstand current
Confirmed per project
kA
1 min power-frequency withstand
42
kV
Lightning impulse withstand
75
kV
Cubicle width
550 / 600 / 650 / 800 / 1000
mm
Cubicle depth
1100 / 1340 / 1400 / 1450 / 1500 / 1650
mm
Cubicle height
2000 / 2100 / 2200 / 2300
mm
Degree of protection
IP4X; IP2X with the breaker door open
Mass
300, including the withdrawable truck
kg

Product FAQs

It need not be uniform. Five widths are available — 550, 600, 650, 800 and 1000 mm — chosen per cubicle against its rated current and component fit: small feeders take 550 or 600 while large incomers and bus-ties widen as needed. Mixing widths in one line-up is the normal approach and makes the total length shorter than a single-width arrangement. The point to watch is that the busbar has to run continuously across cubicles of different width, and ETENZ works that transition out at drawing stage.

It is this model’s main busbar rating, with distribution busbars also available to 4000 A. The typical places that need it are substation main incomers, large station-service supplies in power plants, and any line-up carrying many circuits on one busbar that should not be sectionalised. Where the busbar current falls short, the alternatives are sectionalising or adding a bus-tie, and both add cubicles and floor area. Send the total line-up load and whether sectionalising is acceptable, and whether 4000 A is a requirement or headroom becomes clear.

From the switchroom civil conditions first, with the electrical layout worked out afterwards. Depths run 1100 to 1650 mm in six steps and heights 2000 to 2300 mm in four. The switchroom depth has to take the cubicle depth plus front operating and maintenance space and the truck withdrawal travel, and the clear height has to take the cubicle plus the busbar bridge and top duct. Once those are set, busbar sizes and component layout are arranged in what remains. Send the switchroom layout with clear height and it can be confirmed during quotation.

On capacity and width. A 4000 A main busbar takes KYN550-12, the highest busbar rating in the series. A wide fault range with rated current to 3150 A takes KYN28A-12. A severely limited switchroom area, where 630 to 1600 A is acceptable, takes YF-KYN450-12 at 475 to 550 mm wide and 1100 mm deep. The series page carries the full five-model comparison.

Four things give a preliminary scheme: the single-line diagram, rated voltage and total line-up current, the system fault capacity, and the switchroom dimensions with clear height. For a contract-grade quotation, add each cubicle’s primary scheme and rated current, control supply type and voltage, metering and protection requirements, cable entry arrangement and cable sizes, communication interfaces, and the standards and document list for the destination market.

Yes. Switchgear is supplied as equipment while an MV switchgear E-House or power module is supplied as an enclosure — the first is the panel itself, the second covers the enclosure, equipment layout, auxiliary systems and interface integration. The selectable widths help here, since the line-up can be packed more closely to a given module length. Where it goes inside as the primary equipment, ETENZ details the line-up arrangement, busbar connections and in-module interfaces, and the delivery boundary is settled once at contract stage.

Related Solutions

Prefabricated Infrastructure

Prefabricated E-House Project Delivery Solution

ETENZ delivers configurable prefabricated E-House projects for electrical equipment integration, covering enclosure manufacturing, layout, wiring paths, factory checks, interface coordination, and OEM/ODM cooperation.

Prefabricated E-House Project Delivery Solution
Custom Prefabricated Enclosure Manufacturing Solution
MV/LV Switchgear E-House Integration Solution
High-Voltage VFD Prefabrication Solution
High-Altitude Integrated E-House OEM Solution