It saves in the no-load column. No-load loss at 630 kVA is 320 W against 570 W for the silicon-steel S13, a difference of 250 W; at 30 kVA it is 33 W against 80 W, a difference of 47 W and close to six tenths in proportion. Load loss is unchanged — both are 6200 W at 630 kVA. The annual saving is the no-load difference times the annual energised hours, independent of load factor. Send the annual energised hours and the tariff and the figure can be calculated.

Amorphous Alloy Oil-Immersed Transformer
For distribution contractors, panel builders and industrial project owners: the ETENZ amorphous alloy oil-immersed transformer covers 30–2500 kVA three-phase and 5–160 kVA single-phase at 10 kV and 20 kV, with no-load loss around half that of a silicon-steel unit of the same rating — for distribution points that stay energised all year at a low load factor.
Key Metrics
Product Features
No-load loss halved
No-load loss at 630 kVA is 320 W against 570 W for the silicon-steel S13 of the same rating; at 30 kVA it is 33 W against 80 W. The smaller the rating the larger the reduction, approaching six tenths at the small end. No-load loss is produced without interruption all year and does not depend on the load factor.
No-load loss halved
No-load loss at 630 kVA is 320 W against 570 W for the silicon-steel S13 of the same rating; at 30 kVA it is 33 W against 80 W. The smaller the rating the larger the reduction, approaching six tenths at the small end. No-load loss is produced without interruption all year and does not depend on the load factor.
No-load loss halved
No-load loss at 630 kVA is 320 W against 570 W for the silicon-steel S13 of the same rating; at 30 kVA it is 33 W against 80 W. The smaller the rating the larger the reduction, approaching six tenths at the small end. No-load loss is produced without interruption all year and does not depend on the load factor.
Load loss unchanged
Load loss at 630 kVA is 6200 W, cell for cell the same as the S13 of that rating — changing the core material changes the magnetising circuit, not the resistive loss in the windings. The whole gain sits in the no-load column, so the lower the load factor and the longer the annual energised hours, the better the arithmetic works out.
Two series
Three-phase 30–2500 kVA covers the usual distribution points; single-phase 5–160 kVA serves rural networks and scattered loads, with 2×(0.22–0.24) kV on the low-voltage side, vector group II0 or II6, and 3.5% short-circuit impedance across the whole series.
Three classes
The 6 kV class carries 25 kV power-frequency withstand and 75 kV lightning impulse; 10 kV carries 35 kV and 95 kV; 20 kV carries 55 kV and 125 kV. Highest voltage for equipment is 7.2, 12 and 24 kV respectively, checked against the system voltage and the overvoltage protection arrangement.
Wound core
Amorphous ribbon is thin and brittle, so the core is wound rather than stacked and its geometry differs from a silicon-steel unit. External interfaces are unaffected, but the weight of the active part, the oil volume and the overall dimensions cannot be carried over from a silicon-steel unit of the same rating.
Product Details

The leading S is three-phase, B means the low-voltage side uses a copper foil coil, and H marks the amorphous alloy core — that position is what separates this series from the silicon-steel version in the designation. The digits that follow are the performance-level code, and M means the sealed construction. Rated capacity and rated high voltage follow the code. SBH15-M-630/10 therefore reads: three-phase, copper foil low voltage, amorphous core, performance level 15, sealed, 630 kVA, 10 kV. SBH21 and SBH25 are higher performance levels of the same construction.

Almost all of a transformer’s no-load loss is produced in the core: the alternating field causes hysteresis and eddy-current loss in the core material, and both persist as long as the winding is energised, regardless of how much load is drawn. Amorphous alloy ribbon has no long-range order in its atomic arrangement, so its hysteresis loop is narrow, and the ribbon is far thinner than a silicon-steel lamination; both losses fall together. In the parameter table that shows as 320 W against 570 W at 630 kVA, 450 W against 830 W at 1000 kVA, and 33 W against 80 W at 30 kVA. The smaller the rating, the larger the proportional reduction. The load-loss column does not follow — both are 6200 W at 630 kVA. Resistive loss in the winding is set by conductor cross-section and current, and changing the core material does not touch it.
Because the whole gain lands in the no-load column, it is independent of load factor and proportional to energised hours. Distribution points that stay energised for long hours at a low average load factor — rural network substations, municipal lighting, scattered small loads, standby transformers idling for long periods — return the highest annual saving per unit of extra cost. The reverse also holds: on an industrial main transformer running at seventy or eighty per cent year-round, load loss dominates the total, the amorphous share of the saving is proportionally small, and the payback stretches out. The calculation needs only three inputs: annual energised hours, average load factor and tariff. Once rating and generation are fixed, no-load and load loss for both core materials are in the table, and ETENZ works the difference out against the hours and tariff of the project before the rating is settled.
The single-phase range covers twelve capacity steps from 5 to 160 kVA, with 2×(0.22–0.24) kV or 0.22–0.24 kV on the low-voltage side, vector group II0 or II6, and 3.5% short-circuit impedance across the whole series. There are two ways to use it: a single unit running single-phase, feeding a scattered area dense in single-phase load; or three units grouped and run as a three-phase set. The second suits a line whose load is very unevenly distributed, because capacity can then be set per phase instead of enlarging a whole three-phase transformer for the peak on one phase. Single-phase units also come with either core material, and the amorphous no-load loss is about a third of the silicon-steel one at the same rating — 0.10 kW against 0.37 kW at 160 kVA.
Delivery Scope Options
Single Unit or Complete Package Supply
Scope 1Single Unit or Complete Package Supply
Transformers are supplied as single units against the order schedule, or as a complete package together with the protective enclosure, the temperature controller and the cooling fans. The active part is wound, assembled and routine-tested at the works and shipped as a complete unit; the assembly interface for the accessories follows the transport conditions. Where the transformer is to arrive together with a prefabricated power module, the E-House line takes on the enclosure, the internal arrangement and the foundation fixing, and the transformer is delivered as equipment housed within it.
Scope Includes:
Single Unit or Complete Package Supply
Scope 1Single Unit or Complete Package Supply
Transformers are supplied as single units against the order schedule, or as a complete package together with the protective enclosure, the temperature controller and the cooling fans. The active part is wound, assembled and routine-tested at the works and shipped as a complete unit; the assembly interface for the accessories follows the transport conditions. Where the transformer is to arrive together with a prefabricated power module, the E-House line takes on the enclosure, the internal arrangement and the foundation fixing, and the transformer is delivered as equipment housed within it.
Scope Includes:
Technical Specifications
| Parameter | Specification |
|---|---|
| Product form | Oil-immersed distribution transformer with an amorphous alloy core, three-phase and single-phase |
| Rated capacity, three-phase | 30–2500 kVA |
| Rated capacity, single-phase | 5, 10, 16, 20, 30, 40, 50, 63, 80, 100, 125, 160 kVA |
| Rated high voltage | 10 kV (6, 6.3, 10.5, 11 kV); a separate table covers the 20 kV class |
| Rated low voltage, three-phase | 0.4 kV |
| Rated low voltage, single-phase | 2×(0.22–0.24) kV or 0.22–0.24 kV |
| Off-circuit tapping range | ±5% or ±2×2.5% |
| Vector group, three-phase | Dyn11; Yyn0 available where the core is a three-phase three-limb type |
| Vector group, single-phase | II0 or II6 |
| Short-circuit impedance, three-phase | 4.0% (≤500 kVA); 4.5% (630–1600 kVA); 5.0% (2000–2500 kVA) |
| Short-circuit impedance, single-phase | 3.5% across the series |
| No-load loss (630 kVA three-phase) | 320 W |
| Load loss (630 kVA three-phase) | 6200 W |
| No-load loss against silicon steel of the same rating | 30 kVA 33 W vs 80 W; 630 kVA 320 W vs 570 W; 2500 kVA 900 W vs 1830 W |
| No-load current (630 kVA three-phase) | 0.3% |
| Insulation level (6 kV class) | Highest voltage for equipment 7.2 kV; power-frequency withstand 25 kV/min; lightning impulse full wave 75 kV |
| Insulation level (10 kV class) | Highest voltage for equipment 12 kV; power-frequency withstand 35 kV/min; lightning impulse full wave 95 kV |
| Insulation level (20 kV class) | Highest voltage for equipment 24 kV; power-frequency withstand 55 kV/min; lightning impulse full wave 125 kV |
| Core construction | Wound core of amorphous alloy ribbon |
| Cooling | ONAN oil-immersed natural cooling |
| Service conditions | Outdoor; maximum +40 °C, minimum −25 °C, altitude not above 1000 m |
Product FAQs
At distribution points energised for long hours at a low average load factor — rural network substations, municipal lighting, scattered small loads, standby transformers on long idle duty. The gain comes only from no-load and is unaffected by how much load is carried, so the lower the load factor the larger the share amorphous removes from the total loss. On an industrial main transformer running at seventy or eighty per cent all year, load loss dominates and the payback stretches out noticeably; there the comparison worth making is against generations such as S20/S22, where both columns fall.
Amorphous ribbon is thin and brittle, so the core is wound rather than stacked and the assembly and clamping differ from a silicon-steel unit; winding construction and short-circuit design do not change with the core material, and short-circuit withstand is calculated for the rating and impedance chosen. Where a project calls for short-circuit test records or third-party test evidence, they are provided separately for the type and configuration selected.
The interfaces line up; the dimensions may not. Bushing positions and low-voltage terminals follow the standard, but the wound core has a different geometry from a stacked one, so the weight of the active part, the oil volume and the overall dimensions are a separate set of figures. Before an in-place replacement, check the wheel gauge, load-bearing capacity and clear space of the existing foundation and fence, and whether the oil pit volume is sufficient. Take the values from the actual data for the rating and core chosen rather than from a silicon-steel table of the same rating.
On lines dense in single-phase load or with very uneven load distribution. A single unit can run alone to feed single-phase load, or three units can be grouped and run as a three-phase set; the second lets capacity be set per phase instead of enlarging a whole three-phase transformer for the peak on one phase. The single-phase range covers twelve capacity steps from 5 to 160 kVA at 3.5% impedance throughout, and is likewise available with either core material.
Yes. Where it travels with the module, the prefabricated power module line takes on the enclosure, the internal arrangement and the foundation fixing, and the transformer leaves the works as equipment inside it. An oil-immersed unit inside a module needs an oil pit or oil-retention arrangement sized on the oil volume; the oil volume of an amorphous unit differs from a silicon-steel one of the same rating, so set it out from the actual data. Ventilation openings, clear cooling space and maintenance aisles are settled in one pass at the layout drawing stage.
Related Solutions
Prefabricated E-House Project Delivery Solution
ETENZ delivers configurable prefabricated E-House projects for electrical equipment integration, covering enclosure manufacturing, layout, wiring paths, factory checks, interface coordination, and OEM/ODM cooperation.





Related Products

Integrated E-House

MV Switchgear E-House

Containerized MV Switchgear E-House

Oil-Immersed Distribution Transformer

Triangular Wound Core Oil-Immersed Transformer








