Single-phase pole-mounted oil-immersed transformer

Single-Phase Pole-Mounted Oil-Immersed Transformer

For distribution contractors, rural network upgrades and municipal projects: the ETENZ single-phase pole-mounted oil-immersed transformer covers twelve capacity steps from 5 to 160 kVA in a fully sealed tank hung straight on the pole, used singly for single-phase load or in groups of three run as a three-phase set.

Distributed Node Power Supply

Key Metrics

5–160kVA
Capacity
3.5%
Impedance
650kg
Weight 160 kVA
II0 / II6
Vector group

Product Features

Feature icon

Pole mounted

A cylindrical fully sealed tank clamped straight onto the pole, with no foundation, fence or transformer platform. At 160 kVA the total weight is 650 kg and at 5 kVA only 135 kg, which a single pole carries, so the civil works come to almost nothing.

Feature icon

Pole mounted

A cylindrical fully sealed tank clamped straight onto the pole, with no foundation, fence or transformer platform. At 160 kVA the total weight is 650 kg and at 5 kVA only 135 kg, which a single pole carries, so the civil works come to almost nothing.

Product Details

A cylindrical fully sealed tank is clamped directly to the pole, with two bushings on the high-voltage side and the low-voltage side brought out from the tank wall. Foundation, fence, transformer platform and earthing grid construction all fall away, and the civil scope is essentially removed. Weight rises gently with rating: 135 kg at 5 kVA, 350 kg at 50 kVA, 650 kg at 160 kVA. A standard single pole carries the whole capacity range, and pole type and burial depth follow the local distribution standard. In the fully sealed construction the oil never meets air, so no topping-up or filtering is needed in service and there is no conservator or breather. Where maintenance access at the top of a pole is awkward, one fewer item to inspect periodically is worth more than it would be at ground level. Where the units are supplied against a network upgrade schedule, ETENZ confirms pole type, clamp spacing and the outgoing direction with the line design before manufacture.

Clamp mounting and high- and low-voltage terminations of a single-phase pole-mounted transformer

The low-voltage side comes in two arrangements: a 2×(0.22–0.24) kV dual winding brought out, or a single 0.22–0.24 kV winding. The dual winding can be connected in series for 0.44–0.48 kV, in parallel to double the current, or brought out as two independent 0.22 kV circuits, settled against the local low-voltage system and the way the load is connected. The vector group is II0 or II6 and the short-circuit impedance is 3.5% across the whole series — the same value on all twelve capacity steps, unchanged by rating, which is not how a three-phase unit behaves. Where three units are grouped and run as a three-phase set, their ratings need not be equal and can be chosen per phase against the real load. Matching impedance is the condition for parallel operation, met naturally when the three are the same type and rating; where the ratings differ, the resulting unbalance has to be calculated.

Delivery Scope Options

Scope 1

Single Unit or Complete Package Supply

Transformers are supplied as single units against the order schedule, or as a complete package together with the protective enclosure, the temperature controller and the cooling fans. The active part is wound, assembled and routine-tested at the works and shipped as a complete unit; the assembly interface for the accessories follows the transport conditions. Where the transformer is to arrive together with a prefabricated power module, the E-House line takes on the enclosure, the internal arrangement and the foundation fixing, and the transformer is delivered as equipment housed within it.

Scope Includes:
Single unit or complete package
Complete-unit shipment and assembly interface
Foundation and fixing interface
In-cabin delivery handled by the E-House line
Scope 1

Single Unit or Complete Package Supply

Transformers are supplied as single units against the order schedule, or as a complete package together with the protective enclosure, the temperature controller and the cooling fans. The active part is wound, assembled and routine-tested at the works and shipped as a complete unit; the assembly interface for the accessories follows the transport conditions. Where the transformer is to arrive together with a prefabricated power module, the E-House line takes on the enclosure, the internal arrangement and the foundation fixing, and the transformer is delivered as equipment housed within it.

Scope Includes:
Single unit or complete package
Complete-unit shipment and assembly interface
Foundation and fixing interface
In-cabin delivery handled by the E-House line

Technical Specifications

Product form
Single-phase fully sealed oil-immersed transformer, pole-mounted
Rated capacity
5, 10, 16, 20, 30, 40, 50, 63, 80, 100, 125, 160 kVA
Rated high voltage
6, 6.3, 10, 10.5, 11 kV
Rated low voltage
2×(0.22–0.24) kV or 0.22–0.24 kV
Off-circuit tapping range
±5% or ±2×2.5%
Vector group
II0 or II6
Short-circuit impedance
3.5% across the series, unchanged by rating
No-load loss (silicon steel core)
0.04 kW at 5 kVA to 0.37 kW at 160 kVA
Load loss
0.15 kW at 5 kVA to 2.37 kW at 160 kVA
No-load loss (amorphous core)
0.02 kW at 5 kVA to 0.10 kW at 160 kVA
No-load current
4.0% at 5 kVA falling to 1.7% at 160 kVA
Total weight
135 kg at 5 kVA to 650 kg at 160 kVA
Product version
Standard or self-protected
Core material
Silicon steel or amorphous alloy
Tank construction
Cylindrical fully sealed; no topping-up or filtering in service
Mounting
Clamped to the pole; no foundation or transformer platform
Operating arrangement
One unit single-phase, or three grouped as a three-phase set
Product standards
GB 10318, IEC 76, ANSI C57.12.00, ANSI C57.12.20
Cooling
ONAN oil-immersed natural cooling
Service conditions
Outdoor; maximum +40 °C, minimum −25 °C, altitude not above 1000 m

Product FAQs

In distribution areas where load is scattered, individual points are small and low-voltage runs are long. Several small single-phase transformers sited near the load shorten the low-voltage supply radius, and voltage drop and line loss come down with it; the longer the line and the more scattered the load, the clearer the gain. Where three-phase load dominates or load is concentrated, a three-phase unit is still the answer. The inputs for the judgement are low-voltage line length, conductor cross-section, load distribution and annual consumption.

It follows the inspection and maintenance conditions. The self-protected version integrates the high-voltage fuse, the low-voltage circuit breaker and overload protection into the unit, clearing an internal fault or a low-voltage overload locally rather than depending on an upstream operation — which suits long rural feeders with long inspection intervals and difficult fault location, and keeps a fault confined to one unit. The standard version is the transformer alone, with protection mounted separately on the pole or covered upstream; where inspection is easy and upstream protection is thorough, it is both more flexible and cheaper.

In no-load loss: at the same rating the amorphous core is about a third of the silicon-steel one — 0.10 kW against 0.37 kW at 160 kVA — while load loss is essentially the same. A pole-mounted transformer stays energised all year at a low average load factor, so no-load loss takes a large share of the annual energy, and with many units in service the cumulative difference is substantial. The payback follows directly from the number of units, the annual energised hours and the tariff.

The three ratings need not be equal and can be chosen per phase against the real load — that is exactly the value of grouping, since a whole three-phase transformer need not be enlarged for the peak on one phase. The condition is the impedance requirement for parallel operation: met naturally when the three are the same type and rating, and where the ratings differ, three-phase unbalance and neutral current have to be calculated. Connection arrangement and low-voltage system are settled together at the design stage.

A dual winding is brought out, with three ways to connect it: in series for 0.44–0.48 kV, in parallel to double the current, or as two independent 0.22 kV circuits. The choice follows the local low-voltage system and the way the load is connected. A single 0.22–0.24 kV winding is available as an alternative. State the low-voltage system, the connection and the termination arrangement together when ordering.

The single-phase capacity range is narrow, 5 to 160 kVA, and the design carries one impedance value through the whole series rather than stepping it with rating as a three-phase unit does. In practice the low-voltage short-circuit current then varies essentially in proportion to rating, and impedance matching for units in parallel or in a group is simple. Take this value when setting low-voltage protection.

Related Solutions

Prefabricated Infrastructure

Prefabricated E-House Project Delivery Solution

ETENZ delivers configurable prefabricated E-House projects for electrical equipment integration, covering enclosure manufacturing, layout, wiring paths, factory checks, interface coordination, and OEM/ODM cooperation.

Prefabricated E-House Project Delivery Solution
Custom Prefabricated Enclosure Manufacturing Solution
MV/LV Switchgear E-House Integration Solution
Synchronous Condenser Electrical E-House Integration Solution
High-Voltage VFD Prefabrication Solution